| Subject: | Re: Propane Heresy - Can you retrofit Westy for alternate use of Coleman fuel? |
| From: | David Beierl |
| Date: | Thu, 9 May 2002 11:46:45 -0400 |
At 04:11 AM 5/9/2002, developtrust wrote: >I was told by the authorized service person who installed my new valves that >this is the way to do it. > >William One of you is misunderstanding the other. You're talking about introducing 50-200 psi into a system designed for about 0.4 psi. The fridge won't run, the stove burners will be trying to pass half a million BTU's per hour instead of 5,000, and I suspect that the second-stage regulator diaphragm might burst. david -- David Beierl - Providence, RI http://pws.prserv.net/synergy/Vanagon/ '84 Westy "Dutiful Passage" '85 GL "Poor Relation"