| Subject: | Re: Door electrics problem |
| From: | George Goff |
| Date: | Sun, 20 Feb 2005 09:13:17 EST |
In a message dated 2/19/05 7:40:16 PM, felder@KNOLOGY.NET writes: << It's like there's a voltage drop to some point below which the motor doesn't run. >> You have a voltage drop all right, but it is not across the motor. Connect one meter lead to a solid ground and take voltage readings at every connection point from the motor terminal back to the line side of its fuse WITH THE CIRCUIT LOADED. Or start at the supply side of the fuse and go towards the motor. Loaded down, nearly all of the voltage drop will appear across any high resistance connection, whereas, unloaded you can take voltage readings all day and never see a problem. George